NEW QUESTION # 54
What is typically considered the demarcation point for electrical utility at a data center?

  • A. The generator
  • B. The transformer
  • C. The UPS
  • D. The switchboard

Answer: B

Explanation:
Explanation


NEW QUESTION # 55
What is the recommended amount of fuel supply to be available to a class F0 data center?

  • A. 24 hours
  • B. 12 hours
  • C. 48 hours
  • D. None - No requirements

Answer: D


NEW QUESTION # 56
What is the maximum recommended number of racks in an aisle?

  • A. 10 racks
  • B. 40 racks
  • C. 30 racks
  • D. 20 racks

Answer: D


NEW QUESTION # 57
What is the recommendation regarding row length?

  • A. None
  • B. Maximum twenty-five racks in each row only
  • C. All
  • D. Ten Racks in Length
  • E. Do not exceed 20 racks in length and dead-end rows not to exceed ten racks long

Answer: E


NEW QUESTION # 58
where should the secured storage area be located?

  • A. adjacent to the non-secured loading dock
  • B. adjacent to the secured loading dock
  • C. adjacent to security offices
  • D. far away as possible from secure data
  • E. None of above

Answer: B


NEW QUESTION # 59
What is the recommended headroom for overhead cable tray?

  • A. 9"
  • B. 6"
  • C. 12"
  • D. 3"

Answer: C


NEW QUESTION # 60
Why do larger data centers require more H DAs?

  • A. to reduce energy consumption and carbon footprint
  • B. to ensure maximum horizontal cable lengths are not exceeded and to avoid cable congestion
  • C. to provide redundancy and failover mechanisms
  • D. to increase server processing speed by minimizing latency

Answer: B


NEW QUESTION # 61
What is the minimum slab floor to ceiling height recommended?

  • A. 15feetminimmum
  • B. 16feetminimum
  • C. 14feetminimum
  • D. 12feetminimum

Answer: A


NEW QUESTION # 62
What is the minimum distance recommended between a data center's backup generator and the main data center building?

  • A. 40 feet
  • B. 20 feet
  • C. 10 feet
  • D. 30 feet

Answer: D


NEW QUESTION # 63
What is the highest allowable elevation for a data center site?

  • A. 5,000 ft
  • B. 12,500 ft
  • C. 2,500 ft
  • D. 7,500 ft
  • E. 10,000 ft

Answer: E


NEW QUESTION # 64
What is the formula for reliability of components in parallel?

  • A. R = RA1 / RA2
  • B. R = 1 - ([1-RA1) * (1-RA2)]
  • C. R = RA1 + RA2
  • D. R = RA1 - RA2

Answer: B


NEW QUESTION # 65
What three things limit the amount of IT equipment per rack?

  • A. fire suppression system technology, humidity levels, and network speed
  • B. power constraints, cooling constraints and lastly, rack space
  • C. staffing availability, security measures, and access points
  • D. sustainability goals, partitioning requirements, and compliance mandates

Answer: B


NEW QUESTION # 66
What is the recommended humidity range for a data center?

  • A. 20-30%
  • B. 50-60%
  • C. 60-70%
  • D. 30-40%
  • E. 40-50%

Answer: E


NEW QUESTION # 67
Where is the recommended location for remote power panels?

  • A. suspended from ceiling
  • B. outside the building
  • C. inside a sealed room
  • D. at one or both ends of an equipment row

Answer: D


NEW QUESTION # 68
What is the appropriate fire rating requirements for a command center?

  • A. 3 hours
  • B. 2 hours
  • C. 1 hour
  • D. 1/2 hour

Answer: C


NEW QUESTION # 69
what is the ANSI/TIA-942 recommended operational temperature

  • A. -10°C to +45°C
  • B. 60F to 75F
  • C. 80F to 90F
  • D. 68F to 77F

Answer: D


NEW QUESTION # 70
What's the maximum number of racks in an aisle if one end has no exit?

  • A. 15 Racks
  • B. 5 racks
  • C. 10 racks
  • D. It doesn't matter

Answer: C


NEW QUESTION # 71
What are three reasons for locating the power distribution unit outside the computer room?

  • A. reduces cable congestion, prevents water damage, provides better access points
  • B. lowers electricity costs, improves network speed, enhances security measures
  • C. removes maintenance item, removes a source of heat, allows P D U to occupy less expensive space
  • D. increases cooling efficiency, eliminates fire hazard, minimizes noise pollution

Answer: C


NEW QUESTION # 72
What 3 standards books should be followed for data center grounding and bonding?

  • A. UL 467, UL 96A and NFPA 70
  • B. TIA 942, TIA 607 and IEEE 1100
  • C. TIA 568, ANSI/TIA-606-B and TIA 568-C.1
  • D. ASHRAE Standard 90.1, ASHRAE Standard 62.1 and ASHRAE Standard 55

Answer: B

Explanation:
Explanation


NEW QUESTION # 73
Apart from marine cargo ports, hazardous material transport roadways, transportation roadways, and flight paths, what other things should a data centre be at least one mile away from?

  • A. Waste-disposal units and dumpsites only.
  • B. Fireworks manufacturing companies only.
  • C. All of The Above
  • D. Petroleum storage installations like petrol stations & oil storage facilities only.

Answer: C


NEW QUESTION # 74
......